Inspection Status: Partial Approval
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 07/27/2004 |
SIGN ELECTRIC |
|
Partial Approval |
IVRS - Inspection :*/ 1) PLEASE FINISH #4 AND 5 OF PREVIOUS INSPECTION |
| 02/02/2004 |
SIGN ELECTRIC |
|
Denied |
IVRS - Inspection 0999*/ 1) CANNOT ENTER SIGN THRU ACCESS COVER. 2) UNSWITCHED ROMEX CONDUCTOR TO BE ISOLATED ENTIRE RUN TO SWITCH. 3) A COVER PLATE IS NEEDED AND FILL UNUSED OPENING ON JUNCTION BOX. GROUND JUNCTION. 4) BOND SIGN ENCLOSURE. 5) M/C CABLE TO TERMINATE TO CONDUIT/SEALTITE SYSTEMS. 6) LABEL SIGN CIRCUIT. 7) PLEASE CALL AND HAVE ADDRESS CORRECTED. THIS IS 7601 E SPEEDWAY. |