Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/12/2005 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :*CORRECTIONS OK |
| 01/10/2005 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) RETURN AIR DUCT INSULATE RETURN AIR PIPE IN CRAWL SPACE & DUCT DOWN TO ?? AT REAR OF FURNACE. ONE INCK ( 1S) DUCT WRAP OK. 2) PROVIDE COMB AIR IN LOWER 12" OF FURNACE RM. LOCATION. LOWER PORTION OF DOOR OK ELBOW DOWN FROM UPPER EXISTING COMBUSTION OPENING OK. 3) STABILIZE 3/4" GAS LINE TO WALL ?? LINE SHOULD BE VIBRATION FREE. |