Inspection History: MECHANICAL - FINAL
Permit Number - T04ME00857
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ALL CORRECTIONS HAVE BEEN MADE. | |
| 01/11/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DO NOT USE WHITE WIRES FOR VOLTAGE . TAPE WIRES WITH BLACK TAPE IN DISCONNECT & CIRCUIT PANEL. 2) DO NOT PUT 2 WIRES ONTO 1 LUG IN THE DISCONNECT TO POWER EVAP. COOLER. PROVIDE A SEPARATE CIRCUIT FOR COOLER. 3) CONDENSATE MUST TERMINATE WITHIN 6" OF THE GROUND & DIVERT THE WATER AWAY FROM THE HOUSE. THE VENT ON THE TRAP MUST BE DOWNSTREAM OF THE TRAP RECALL FOR INSPECTION. |