Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/09/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ALL CORRECTIONS HAVE BEEN MADE.
12/08/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)DON'T REDUCE CONDENSATE PUMP DISCHARGE TO 1/4" STAY 3/8 PROVIDE HOSE CLAMPS ON PLASTEC HOSE 2)PROVIDE A TRAP ON CONDENSATE DRAIN LINE 3)ISOLATE SUCTION LINE FROM SCRAPING ON COIL CABINET.