Permit: T04ME00792

Parcel: 133143540


Addresses:

7022 E CALLE CERCA

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/07/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/16/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/PERMANENTLY INDENTIFY DATA PLATE WITH PROPER HEAT STRIP INSTALLED. BLUE INK PEN IS NOT PERMANENT. FUSE THE HEAT STRIP ACCORDING TO THE DATA PLATE.. 35 AMP IS TOO SMALL. RECALL FOR INSPECTION
12/09/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/CONNECT THE EMT CONDUIT CORRECTLY TO THE FITTING ON THE DISCONNECT. IDENTIFY INSIDE THE DISCONNECT OR ON THE DATA PLATE THE SIZE ELEC. HEATER USED. SECURE THE ELEC. DISCONNECT. SEAL ANY HOLES IN THE BACK OF THE DISCONNECT.