Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04ME00693
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
04/26/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : VENT CONNECTOR MUST BE INCREASED TO 4" AT OUTLET OR FURNACE. CONDENSATE VENT MUST BE DOWNSTREAM OF THE TRAP OR CAP OFF. DOUBLE WALL FITTINGS IN ATTIC UPSIDE DOWN. PIECE OF VENT PIPE BROKEN. EXTEND 2' ABOVE COOLER. |
|
03/28/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VERIFY COMBUSTION SUPPLY/RELIEF 2. PROPERLY PITCH FLUE 3. AIR RETURN MUST BE ISOLATED FROM GAS LINES, FURNACE COMPARTMENT, ETC. 4. SHUT-OFFS FOR GAS AND ELECTRIC DISCONNECTS MUST BE READILY ACCESSIBLE. |
|
02/01/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* INSUFFICIENT CLEARANCE TO WOOD, DOOR CASING & DOOR, REFRIG. LINE ARMAFLEX INSUL, ETC. 1) RECOMMEND B-1 VENT DOWN TO FURN. 2) MUST MAINTAIN INCLINED PITCH UP TO TERMINATION. 3) CONCEAL CONTROL WIRING ON ROOF, EXPOSED TO SEEN. 4) CONN?? VERIFY COMBUSTION AIR VENT FROM CEILING OF FURN. RM. |