Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/20 PSI TEST IS OK. CORRECTIONS HAVE BEEN MADE. | |
| 11/04/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)REMOVE THE GAS SHUT OFF VALVES FROM ALL WALL HEATERS & CAP OFF GAS LINES. PROVIDE A MIN. 10LB PRESSURE TEST ON ALL NEW GAS PIPING. 2)EXTEND CONDENSATE DRAIN TO WITHIN 6" OF THE GROUND & DIVERT THE WATER AWAY FROM THE HOUSE & THE FOUNDATION. 3)IDENTIFY THE CIRCUIT TO THE NEW A/C UNIT |