Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ALL CORRECTIONS HAVE BEEN MADE. | |
| 11/12/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)YOU CANNOT POWER THE EVAP COOLER OFF OF THE SAME CIRCUIT AS THE A/C UNIT & YOU MUST HAVE A COMMON WIRE FOR POWER TO THE EVAP COOLER. YOU CANNOT USE A GROUND WIRE AS COMMON. PROVIDE A SEPERATE CIRCUIT TO POWER THE EVAP. COOLER. 20 ANY FUSE IS TOO LARGE FOR THE EVAP. COOLER. 2)DRAINS FROM A/C UNIT & EVAP COOLER CANNOT DRIP OVER THE EDGE OF THE ROOF. TERMINATE WITHIN 6" OF THE GROUND & DIVERT THE WATER AWAY FROM THE HOUSE & THE FOUNDATAION. 3)ALSO YOU CANNOT PUT 2 WIRES ON 2 LUG IN A DISCONNECT |