Permit: T04ME00683

Parcel: 114471690


Addresses:

7591 E RIO VERDE DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/01/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ALL CORRECTIONS HAVE BEEN MADE.
11/12/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)YOU CANNOT POWER THE EVAP COOLER OFF OF THE SAME CIRCUIT AS THE A/C UNIT & YOU MUST HAVE A COMMON WIRE FOR POWER TO THE EVAP COOLER. YOU CANNOT USE A GROUND WIRE AS COMMON. PROVIDE A SEPERATE CIRCUIT TO POWER THE EVAP. COOLER. 20 ANY FUSE IS TOO LARGE FOR THE EVAP. COOLER. 2)DRAINS FROM A/C UNIT & EVAP COOLER CANNOT DRIP OVER THE EDGE OF THE ROOF. TERMINATE WITHIN 6" OF THE GROUND & DIVERT THE WATER AWAY FROM THE HOUSE & THE FOUNDATAION. 3)ALSO YOU CANNOT PUT 2 WIRES ON 2 LUG IN A DISCONNECT