Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ALL CORRECTIOINS HAVE BEEN MADE | |
| 12/01/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/22/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/THE CIRCUIT FOR THE A/C UNIT CANNOT BE USED TO POWER THE EVAP COOLER OR ANY DEVICE CONNECTED TO IT. YOU CANNOT ATTACH 2 WIRES TO 1 LUG IN THE DISCONNECT & YOU CANNOT USE THE GROUND LUGS IN THE DISCONNECT FOR COMMON. CONDUIT IS BROKEN AT PENETRATION TO THE ROOF. THE DISCONNECT CANNOT BE MOUNTED TO A ACCESS PANEL |