Permit: T04ME00670

Parcel: 121113000


Addresses:

4737 E HELEN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/22/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/15/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)PROVIDE A BUSHING WHERE ELEC WIRES PENETRATE THE CABINET OF THE A/C UNIT 2)DO NOT USE WHITE WIRE FOR HIGH VOLTAGE, ONLY USED FOR NEUTRAL 3)SUPPORT CONDENSATE DRAIN EVERY 4'. DO NOT TERMINATE INTO A SEWER VENT 4)SUPPORT GAS LINE ON ROOF WITH BLOCKS & CLAMPS OR UNISTRUT. WIRE IS NOT AN APPROVED CLAMPING DEVICE FOR GAS PIPE. 5)PROVIDE A MIN 10 LB TEST ON ALL NEW GAS PIPING. NEED TO SEE WHERE GAS LINE IS CONNECTED INSIDE HOUSE. 6)NEED TO SEE ELEC CIRCUIT PANEL. RECALL FOR INSPECTION