Permit: T04ME00667

Parcel: 138071410


Addresses:

834 W CALLE ALVORD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/28/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/25/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/REMOVE OLD ASBESTOS/TRANSITE VENT PIPE FROM ATTIC & USE DOUBLE WALL VENT PIPE. SINGLE WALL FLEX VENT INSIDE CLOSET MUST HAVE MIN. 6" CLEARANCE FROM DOOR FRAME. USE DOUBLE WALL TO REDUCE CLEARANCE TO 1". DO NOT USE TAPE ON DOUBLE WALL FITINGS. RECALL FOR INSPECTION