Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ALL CORRECTIONS HAVE BEEN MADE. OK TO CLEAR CITATION | |
| 11/08/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/PROVIDE A TRAP ON THE CONDENSATE DRAIN LINE. EXISTING TRAP WAS REMOVED. #8 WIRE IS NOT ADEQUATE FOR 80 AMPS FROM CIRCUIT BREAKER UP TO THE ELECTRICAL DISCONNECT. USE #4. IDENTIFY THE PULL OUT FUSE BANKS, A/C & HEAT STRIP. RECALL FOR INSPECTION |
|
| 10/12/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)SUPPORT THE RETURN DUCT AT THE CANVAS CONNECTOR 2)COVER THE SOUTH SIDE OF THE CANVAS CONNECTOR WITH SHEET METAL 3)BLOCK & CLAMP CONDENSATE DRAIN PIPE EVERY 4' & PAINT W/ LATEX PAINT. VENT ON CONDENSATE TRAP MUST BE DOWNSTREAM OF THE TRAP 4)MARK THE UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED & PROVIDE A SEPERATE CIRCUIT TO THE HEAT STRIP. RECALL FOR INSPECTION |