Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/05/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/IDENTIFY ON THE FAN COIL THE PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. #8 WIRE IS NOT ADEQUATE FOR 60 AMPS. PROVIDE A BUSHING WHERE REFER LINES PENETRATE THE CABINET OF FAN COIL. SECURE THE ELEC DISCONNECT ON THE ROOF. SEAL ALL UNUSED HOLES IN BACK OF DISCONNECT. RECALL FOR INSPECTION |