Permit: T04ME00625

Parcel: 133397670


Addresses:

131 S GOLD MINE LP

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/29/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/CORRECTIONS HAVE BEEN MADE.
09/28/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)50 AMP BREAKER NOT ADEQUATE FOR CONDENSOR, FAN COIL & HEAT STRIP #4 ALUM. WIRE ONLY GOOD UP TO 65 AMPS. PROVIDE A SEPERATE CIRCUIT FOR CONDENSOR & PROVIDE PROPER SIZE BREAKER FOR FAN COIL 2)MARD DATA PLATE ON FAN COIL W/PROPER HEAT STRIP INSTATTED?.