Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/CORRECTIONS HAVE BEEN MADE. | |
| 09/28/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)50 AMP BREAKER NOT ADEQUATE FOR CONDENSOR, FAN COIL & HEAT STRIP #4 ALUM. WIRE ONLY GOOD UP TO 65 AMPS. PROVIDE A SEPERATE CIRCUIT FOR CONDENSOR & PROVIDE PROPER SIZE BREAKER FOR FAN COIL 2)MARD DATA PLATE ON FAN COIL W/PROPER HEAT STRIP INSTATTED?. |