Permit: T04ME00610

Parcel: 134232310


Addresses:

442 S KENYON DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/16/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/CORRECTIONS HAVE BEEN MADE.
09/14/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)20 AMP FUSES NOT ADEQUATE FOR 5KW BEAT STRIP. LABEL INSIDE OF DISCONNECT HEATER SIZE & FUSE SIZE. 2)DO NOT USE WHITE WIRE FOR HIGH VOLTAGE. TAPE ENDS W/BLACK TAPE 3)USE A BUSHING WHERE ELEC. WIRES PASS THRU THE PARTITION INSIDE THE UNIT
RECALL FOR INSPECTION.