Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/CORRECTIONS HAVE BEEN MADE. | |
| 09/14/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)20 AMP FUSES NOT ADEQUATE FOR 5KW BEAT STRIP. LABEL INSIDE OF DISCONNECT HEATER SIZE & FUSE SIZE. 2)DO NOT USE WHITE WIRE FOR HIGH VOLTAGE. TAPE ENDS W/BLACK TAPE 3)USE A BUSHING WHERE ELEC. WIRES PASS THRU THE PARTITION INSIDE THE UNIT RECALL FOR INSPECTION. |