Permit: T04ME00595

Parcel: 135100550


Addresses:

7109 E 32ND PL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/21/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ALL CORRECTIONS HAVE BEEN MADE
09/16/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/PLEASE HAVE Y0UR CONTRACTOR RESCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HOME. 1)PROVIDE SCREWS IN END CAPS ON WATER HEATER FLUE & SCREW TEE TO DOUBLE WALL PIPE. 2)REMOVE VALVE FROM SOFFIT AREA. WE WILL SOAP TEST THE FITTINGS
09/10/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) GAS LINE NOT HOLDING PRESSURE 2) REMOVE THE UNION FROM GAS LINE IN ATTIC AND USE REVESE THREAD COUPLING AND NIPPLE 3) EXTEND LOW COMBUSTION AIR DUCT TO WITHIN 12" OF FLOOR 4) SEAL JOINTS ON RETRUN AIR DUCT 5) DO NOT USE WHITE WIRE FOR LINE VOLTAGE 6) YOU CANNOT CUT THE COVER PLATE ON THE ELECTRIC PANEL. REPLACE THE COVER PLATE. USE THE KNOCKOUT PROVIDED ON THE SIDE OF THE PANEL. PROVIDE A PLUG IN THE HOLE CUT INTO THE SIDE OF THE PANEL. DO NOT USE AN EMT CONNECTOR INSIDE THE PANEL TO CONNECT THE LB. USE AND APPROVED FITTING. IDENTIFY THE CIRCUIT BREAKER. USE ONLY A MURRAY BREAKER IN THE ELECTRIC PANEL. RECALL FOR INSPECTION