Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/17/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio DOUBLE WALL VENT PIPE IS STILL INSTALLED UPSIDE DOWN. READ THE INSTRUCTIONS ON THE PIPE. USE A DOUBLE WALL REDUCER AT CONVECTION TO 5" VENT PIPE. YOUR CANNOT RUN DOUBLE WALL, THEN SINGLE WALL THEN DOUBLE. SUPPORT THE CONDENSATE DRAIN IN THE CLOSET. IF YOU WOULD LIKE TO LEARN ABOUT CONDENSATE TRAPS, READ SECTION 307 FROM THE 2003 IMC. DO NOT USE TAPE TO STRAP THE 3/8 FRAIN LINE TO THE SEWER VENT. FREDDIE 622- 6683. PAY A RE-INSPECTON FEE PRIOR TO NEXT INSPECTION. |
|
| 09/02/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920*/DENIED-PLEASE HAVE YOUR CONTRACTOR SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HOME |
|
| 08/31/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROVIDE A TRAP ON CONDENSATE DRAIN LINE 2) YOU CANNOT ATTACH DBL WALL VENT PIPE INTO SINGLE WALL 3) ALSO DBL WALL IS INSTALLED UPSIDE DOWN 4) DO NOT USE TAPE ON DBL WALL PIPE 5) REMOVE 3/8 COPPER LINE FROM SEWER VENT AND TERMINATE OVER THE TOP OF THE VENT WITH A 1" AIR GAP 6) #10 WIRE NOT ADEQUATE FOR 50 AMP CIRCUIT FROM DISCONNECT TO CONDENSOR 7) DO NOT USE WHITE WIRE FOR LINE VOLTAGE 8) PROVIDE A ROOF JACK AT ELECTRIC PENETRATION THRU ROOF 9) NOTE: SEWER SMELL COMING FROM SUPPLY GRILLS 10) RECALL FOR INSPECTION |