Permit: T04ME00584

Parcel: 121021660


Addresses:

2018 N HOMER AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/28/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/25 PSI TEST
09/21/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND. PROVIDE A ROOF JACK AT ELEC PENETRATION THRU THE ROOF & AT CONDENSATE DRAIN 2)SECURE THE ELEC DISCONNECT. DISCONNECT NOT ACCESSIBLE 3)PROVIDE A MIN. 10LB TEST ON NEW GAS PIPE 4)PROVIDE MIN 2 SCREWS IN ALL JOINTS OF VENT CONNECTOR INCLUDING DRAFT DIVERTER