Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/14/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)60 AMP FUSES TO LARGE FOR 7.68 KW HEAT STRIP. 2)USE A BUSHING WHERE ELEC. WIRES PASS THRU THE PARTITION INSIDE A/C UNIT. 3)#4 ALUMINUM WIRE ONLY ADEQUATE UP TO 65 AMPS. |