Permit: T04ME00552

Parcel: 13340001B

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/27/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/REFER LINES SCRAPING ON SHARP METAL AT CONNECTION TO COIL. ADEQUATELY SUPPORT ELEC. DISCONNECT. DO NOT USE WHITE WIRE FOR HIGH VOLTAGE. TAPE WIRES W/BLACK TAPE AT BOTH ENDS OF WIRE. RECALL FOR INSPECTION