Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2004 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/18/2004 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/DENIED- 1)CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. 2)60 AMP FUSES ARE TOO LARGE. 40 AMP IS MAC. 3)TIGHTEN THE ELEC. SEAL TITE FITTING TO A/C UNIT. 4)BLOCK & CLAMP THE LOW VOLTAGE CONDUIT. 5)PROVIDE A PERMIT FOR THE ELEC UPGRADE & SCHEDULE AN INSPECTION. |
|
| 08/16/2004 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920*/PLEASE HAVE YOUR CONTRACTOR SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HOME |