Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/22/2004 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 11/10/2004 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/SER. ELECT. CIR. BKR. 20 AMP IN PANEL. MINIMUM (DATA PLATE) IS 22.6. MAX. FOR 4 TON, 48,000 BTUH IS 40 AMPS. THIS CIRCUIT NEEDS TO BE INCREASED IN SIZE. GAS PRESS. TEST 1 1/4" GAS LINE AT METER, INDIE? 4 PSI. MUST MAINTAIN MIN. 10 PSI. PIPE ALSONEEDS TO BE SCOTCH COATED |
| 10/26/2004 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/NOT SUFFICENT CLEARANCE TO FRONT OF FURNACE 2)NOT SUFFICENT COMB. AIR 3)UNABLE TO VERIFY LISTING/DISTANCE/CLEARANCE TO FRONT OF FURN. 4) NEED TO OPEN UP ADDITIONAL SPACE ON RIGHT SIDE OF DOOR/ACCESS OPENING |