Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/13/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. 2) 3/8" X 20 GAS FLEX NOT ADEQUET FOR 98000 BTU. SEE LISTING ON FLEX. DO NOT USE THREAD PROTECTORS FOR COUPLINGS. 3) TIGHTEN SEAL TITE FITTINGS AT UNIT & AT CONDUIT CONNECTION. 4) 45 AMP FUSSES TOO LARGE. 40AMP IS MAX. |