Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/12/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) APPROVED |
| 07/08/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) PRESSURE TEST GAS LINE AS PER CONVERSATION |
| 07/02/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) IMPROPER CONDENSATE TERMINATION. 2) INCORRECT FUSE AT UNIT. SEE MIN SIZE FUSE THAT CAN BE USED. 3) GAS LINE (FLEX) ON WEST SIDE UNIT NOT SUFFICIENT FOR 110,000 BTUH. 4) WHAT TYPE DUCT LINER AND THICKNESS USED ON ROOF TOP DUCTS? 5) NEED TO ELIMANATE UNION IN 1" GAS LINE ON ROOF. UNIONS NEED GAS VALVE AHEAD OF LOCATION. |