Permit: T04ME00456

Parcel: 11107248B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/12/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ 1) APPROVED
07/08/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/ 1) PRESSURE TEST GAS LINE AS PER CONVERSATION
07/02/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/ 1) IMPROPER CONDENSATE TERMINATION. 2) INCORRECT FUSE AT UNIT. SEE MIN SIZE FUSE THAT CAN BE USED. 3) GAS LINE (FLEX) ON WEST SIDE UNIT NOT SUFFICIENT FOR 110,000 BTUH. 4) WHAT TYPE DUCT LINER AND THICKNESS USED ON ROOF TOP DUCTS? 5) NEED TO ELIMANATE UNION IN 1" GAS LINE ON ROOF. UNIONS NEED GAS VALVE AHEAD OF LOCATION.