Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04ME00441
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/25/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ 1) ALL CORRECTIONS HAVE BEEN MADE | |
08/05/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SECURE THE ELECTRIC DISCONNECT. SEAL ALL HOLES IN THE BACK OF THE DISCONNECT 2) THE GAS SHUT OFF VALVES MUST PRECEDE THE FLEX CONNECTOR 3) THE VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP 4) RECALL FOR INSPECTION |
|
07/07/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CONDENSATE LINE CAN NO LONGER TERMINATE IN A VENT PIPE 2) UNIT IS OVERFUSED-40 MAX, PRESENTLY 45'S |
|
06/30/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920*/ PLEASE CALL FOR AN INSP WHEN AN ADULT WILL BE PRESENT. IN THE FUTURE, PLEASE ADVISE YOUR CUSTOMER THAT AN INSPECTOR WILL BE SHOWING. |