Permit: T04ME00440

Parcel: 112074180

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/27/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/27/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/ 1) GAS PRESSURE TEST, GAUGE ON ROOF INDICATING 4 PSI, MINIMUM MUST BE 10 PSI 2) CAN'T TERMINATE CONDENSATE PIPING OFF EDGE OF ROOF 3) BETTER CALCULATE GAS PIPING SIZE FURN. IS 120,000 BTUH. CHECK VOLUME OF 1/2" PIPE AND LENGTH