Permit: T04ME00426

Parcel: 119221810


Addresses:

3001 S OBERON RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/08/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/28/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/ 48,000 BTUH COOL. 100 K HT COMB ROOFTOP UNIT. 1) REMOVE FIELD INSTALLED TRAP - UNIT HAS BUILT IN TRAP PROVIDED BY MANUFACTURER. 2) CONDENSATE TERMINATION IS DUMPING ON CONCRETE DRIVEWAY ( NOT CAPABLE OF ABSOBING) DRAIN WTR.