Permit: T04ME00423

Parcel: 12806104A


Addresses:

5601 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/25/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ CORRECTIONS HAVE BEEN MADE.
06/23/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PROVIDE AN OUTSIDE AIR INTAKE ON A/C UNIT. 2) PROVIDE A SUN SHIELD OVER CANVAS CONNECTORS. 3) SECURE THE ELEC. DISCONNECT. #8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT FROM ELEC DISCONNECT TO A/C UNIT. 4) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. GO TO WITHIN 6" OF THE GROUND IN AN AREA THAT CAN ABSORB THE WTR, OR TO AN APPROVED PLBG FIXTURE.