Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ 1) CORRECTIONS HAVE BEEN MADE | |
| 07/14/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) A/C UNIT OVERFUSED AT 45 AMP 2) 20 AMP IS MAX. FUSE SIZE 3) RECALL FOR INSPECTION |
|
| 06/23/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ ROOF TOP EQUIPMENT 1) MARK THE UNIT DATA PLATES WITH PROPER HT STRIP INSTALLED AND FUSE UNIT ACCORDINGLY. 2) SECURE THE ELEC DISCONNECT. 3) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. EXPOSED PVC MUST BE PAINTED WITH LATEX PAINT. BLOCK AND CLAMP EVERY 4' RECALL FOR INSP. |