Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)CONDENSATE DRAIN LINE NOT CONNECTED TO 4 TON UNIT 2)EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE ON 3 1/2 TON UNIT. RECALL FOR INSPECTION |
|
| 08/30/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/DENIED ALL CORRECTIONS FROM PREVIOUS INSPECTION HAVE BEEN IGNORED |
|
| 08/25/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/DENIED-1)CONDENSATE DRAINS CANNOT DRIP OUT OF A SCUPPER. MUST GO TO WITHIN 6" OF THE GROUND 2)THE HANDLE ON THE FUSE BANK FOR THE 3 1/2 TON UNIT IS BROKEN OFF 3)SUCURE THE ELEC. DISCONNET ON TH 4 TON UNIT. 4)PROVIDE FRESH AIR INTAKES ON BOTH UNITS 5)SECURE THE ELEC. CONDUIT ON THE 4 TON UNIT. RECALL FOR INSPECTION |