Permit: T04ME00414

Parcel: 12105013A


Addresses:

5610 E GRANT RD

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/14/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)CONDENSATE DRAIN LINE NOT CONNECTED TO 4 TON UNIT 2)EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE ON 3 1/2 TON UNIT.
RECALL FOR INSPECTION
08/30/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/DENIED
ALL CORRECTIONS FROM PREVIOUS INSPECTION HAVE BEEN IGNORED
08/25/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/DENIED-1)CONDENSATE DRAINS CANNOT DRIP OUT OF A SCUPPER. MUST GO TO WITHIN 6" OF THE GROUND
2)THE HANDLE ON THE FUSE BANK FOR THE 3 1/2 TON UNIT IS BROKEN OFF
3)SUCURE THE ELEC. DISCONNET ON TH 4 TON UNIT.
4)PROVIDE FRESH AIR INTAKES ON BOTH UNITS
5)SECURE THE ELEC. CONDUIT ON THE 4 TON UNIT.
RECALL FOR INSPECTION