Permit: T04ME00395

Parcel: 135111220


Addresses:

7542 E 35TH ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/18/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ ALUMINUM WIRE DOES NOT FIT THE LUGS IN ELEC. DISCONNECT. CORRECT AND RECALL FOR INSPECTION. SPLIT BOLT CONNECTORS CAN BE USED IN A JUNCTION BOX TO SPLICE ALUMINUM TO COPPER. TAPE ANY EXPOSED SPLICES.