Permit: T04ME00370

Parcel: 135081070

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/17/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ ALL CORRECTIONS HAVE BEEN MADE.
06/10/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) CRIMPED ENDS OF VENT CONNECTOR MUST GO WITH THE FLOW. REMOVE TAPE FROM CONNECTION TO DBL WALL. VENT CONNECTOR MUST HAVE SLOPE. ALL JOINTS TO HAVE MIN. SCREWS. 2) ISOLATE COPPER FROM SCRAPING ON COIL CABINET. 3) DO NOT USE AN EMT FITTING TO CONNECT AN LB TO THE CIRCUIT PANEL.