Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/26/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROVIDE MIN. THREE SCREWS IN EACH JOINT OF VENT CONNECTOR. CRIMPED ENDS MUST GO WITH AIR FLOW. DO NOT USE TAPE. 2) TIGHTEN ROMEX CONNECTOR ONTO WIRES. 3) VENT ON CONDENSATE DRAIN SHOULD BE INSTALLED DOWNSTREAM OF THE TRAP. VENT IS NOT REQUIRED. 4) PROVIDE A HOSE CLAMP WHERE PLASTIC HOSE CONNECTS TO PUMP. 5) STRAP REFER LINES TO OUTSIDE WALL. ISOLATE COPPER LINE FROM CONTACTING STEEL. JOINTS ON INSULATION NEED GLUE THEY ARE COMING APART. SEAL AROUND PENETRATION IN ROOF. 6) PLEASE PROVIDE A PERMIT FOR ELEC. UPGRADE AND SCHEDULE AN INSP. 7) IDENTIFY CIRCUIT BREAKERS FOR FURNACE AND A/C |