Permit: T04ME00311

Parcel: 136052380

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/07/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/04/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/TEST ON GAS LINE IS OK. OK TO CONNECT FURNACE. RE SEAL AROUND DUCT PENETRATION THRU ROOF. PROVIDE AN ELECTRICAL PERMIT FOR ELEC. PANEL UPGRADE & SCHEDULE AN ELEC. INSPECTION. AFTER ELEC. INSPECTION HAVE ELEC. INSPECTOR CALL ME TO CLEAR MECHANICAL
07/29/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) 60 POUND PRESSURE GAUGE NOT ACCEPTABLE 2) PROVIDE A PERMIT FOR ELECTRIC UPGRADE
07/01/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) USE A WTRPROOF CONNECTOR WHERE EMT CONNECTS TO TOP OF PANEL. PROVIDE A PERMIT FOR PANEL UPGRADE AND SCHEDULE AN INSP. 2) GAS PRESSURE TEST NOT HOLDING PRESSURE. 60 POUND GUAGE NOT ACCURATE. USE A GUAGE NOT EXCEEDING 30 PSI. 3) 60 AMP CIRCUIT REQUIRES #6 WIRE. RECALL FOR INSP.