Permit: T04ME00309

Parcel: 12109275B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/19/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*CORRECTIONS HAVE BEEN MADE
11/19/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio/CONDENSATE DRAIN LINE STILL NOT SECURED TO EXTERIOR WALL. PROVIDE AN ELBOW AT THE BOTTOM & DIVERT THE WATER AWAY FROM THE HOUSE & FOUNDATION. SECURE THE HUMIDIFIER DRAIN TO THE WALL AT BOTTOM. IDENTIFY BREAKER FOR A/C UNIT TO HUMIDIFIER. #8 WIRE OK FOR 50 AMP CIRCUIT. PAY A RE-INSPECTION FEE PRIOR TO NEXT INSPECTION
06/30/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) #8 WIRE IS NOT ADEQUATE FOR 60 AMP CIRCUIT. TIGHTEN THE SEAL TITE CONNECTION TO THE DISCONNECT. 2) PROVIDE CLAMPS ON THE ELEC CONDUITS AND GAS LINE, NOT TAPE. 3) SECURE THE CONDENSATE DRAIN LINE TO THE EXTERIOR WALL. EXTEND THE HUMIDFIER DRAIN TO WITHIN 6" OF THE GROUND OR CONNECT IT INTO THE CONDENSATE DRAIN PIPE. SECURE THE HUMIDFIER DRAIN. ADD ANOTHER BLOCK UNDER ELEC. CONDUIT. IDENTIFY THE CIRCUIT BREAKER FOR A/C EQUIPMENT. RECALL FOR INSP.