Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ CORRECTIONS HAVE BEEN MADE. | |
| 06/10/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ IDENTIFY CIRCUIT BREAKER FOR CONDENSOR. 40 AMP IS TOO LARGE. 35 AMP IS MAX. RECALL FOR INSP. |