Permit: T04ME00289

Parcel: 117143180


Addresses:

537 S MAIN AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04ME00289

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/09/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/ PRESS TEST INDICATING 15 PSI SYSTEM EMPTY.
05/24/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ TIGHTEN LOOSE ELECT CONNECTION TO A/C UNIT. GAS PRESSURE TEST HAS NO AIR. PROVIDE MIN. 10LB. A/C UNIT OVERFUSED - 30 AMP IS MAX. #10 WIRE NOT ADEQUATE FOR 40 AMP CIRCUIT. USE #8 WIRE OR CHANGE TO 30 AMP BREAKER. DO NOT USE A CHASE NIPPLE TO CONNECT TO SERVICE PANEL. USE A BOND BUSHING IF USING REDUCER WASHERS. RECALL FOR INSP.