Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04ME00289
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
06/09/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*/ PRESS TEST INDICATING 15 PSI SYSTEM EMPTY. | |
05/24/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ TIGHTEN LOOSE ELECT CONNECTION TO A/C UNIT. GAS PRESSURE TEST HAS NO AIR. PROVIDE MIN. 10LB. A/C UNIT OVERFUSED - 30 AMP IS MAX. #10 WIRE NOT ADEQUATE FOR 40 AMP CIRCUIT. USE #8 WIRE OR CHANGE TO 30 AMP BREAKER. DO NOT USE A CHASE NIPPLE TO CONNECT TO SERVICE PANEL. USE A BOND BUSHING IF USING REDUCER WASHERS. RECALL FOR INSP. |