Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) A/C UNIT ALREADY HAS A TRAP BUILT IN TO THE CONDENSATE DRAIN. REMOVE 2ND TRAP AS PER MANUFACTURERS INSTRUCTIONS. 2) CONDENSATE CAN NO LONGER TERMINATE INTO A SEWER VENT. GO TO WITHIN 6" OF THE DIRT OR TO AN APPROVED PLBG RECEPTOR. 3) PROVIDE AN OUTSIDE AIR INTAKE ON A/C UNIT. RECALL FOR INSP. |