Permit: T04ME00250

Parcel: 136030230


Addresses:

8551 E 23RD ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/14/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ ALL CORRECTIONS HAVE BEEN MADE.
05/05/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ THE PLUG ON THE CORD FROM CONDENSATE PUMP CAN NOT BE CUT OFF AND WIRED INSIDE THE FURNACE. RECONNECT SEAM ON REFER LINE INSULATION INSIDE CLOSET. 50 AMP FUSES ARE TOO LARGE. 45 AMP IS MAX FUSE SIZE.