Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ ALL CORRECTIONS HAVE BEEN MADE. | |
| 05/05/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ THE PLUG ON THE CORD FROM CONDENSATE PUMP CAN NOT BE CUT OFF AND WIRED INSIDE THE FURNACE. RECONNECT SEAM ON REFER LINE INSULATION INSIDE CLOSET. 50 AMP FUSES ARE TOO LARGE. 45 AMP IS MAX FUSE SIZE. |