Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/29/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) YOU CANNOT USE AN EMT CONNECTOR TO ATTACH AN LB TO A CIRCUIT PANEL. IF USING REDUCER WASHERS YOU MUST ALSO USE A BOND BUSHING. 2) YOU CANNOT TERMINATE CONDENSATE INTO A RAIN GUTTER that drips onto a sidewalk. go to within 6" of the dirt. also the return air grill is coming off the ceiling. re-attach as needed to get flush with ceiling. |