Permit: T04ME00241

Parcel: 133250440


Addresses:

8601 E ROSEWOOD ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/07/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ ALL CORRECTIONS HAVE BEEN MADE.
05/21/2004 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
05/18/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) DO NOT CONNECT TO THE CIRCUIT PANEL WITH A CHASE NIPPLE. ALSO PROVIDE A BOND BUSHING IF USING REDUCER WASHERS. 2) EXISTING FURNACE FLUE MUST BE CAPPED OFF INSIDE CLOSET. SECURE THE TEE INSIDE CLOSET. ITS ABOUT TO FALL OUT. USE SHEET METAL SCREW TO CAP OFF FLUE. DO NOT USE TAPE. 3) CONDENSATE CANNOT TERMINATE INTO A RAIN GUTTER WITHOUT A DOWNSPOUT. MUST TERMINATE TO WITHIN 6" OF THE GROUND.