Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ THE A/C UNIT IS STILL OVERFUSED AND THERE IS NO FRESH AIR INTAKE AS NOTED FROM PREVIOUS INSP. RECALL. |
|
| 05/14/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920*/ PLEASE CALL FOR AN INSP. WHEN SOMEONE WILL BE HOME. |
|
| 05/07/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNIT OVERFUSED @ 60 AMP. 50 AMP IS MAX FUSE SIZE. 2) PROVIDE AN OUTSIDE AIR INTAKE ON A/C UNIT. INSULATE T-WIRES IN ATTIC. RECALL FOR INSPC |