Permit: T04ME00234

Parcel: 13510150R

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/07/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. RUN DRAIN LINE INTO THE BLDG AND TERMINATE TO AN APPROVED PLUMBING FIXTURE. RECALL FOR INSPECTION
05/25/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) RELOCATE FRESH AIR INTAKE 10' AWAY FROM SEWER VENT, OR RAISE SEWER VENT 2' ABOVE INTAKE. 2) CONDENSATE CANNOT DRAIN ONTO A HARD SURFACE. RELOCATE TO AN APPROVED PLBG RECEPTOR OR TO AN AREA CAPABLE OF ABSOBING THE WTR. RECALL FOR INSP.