Permit: T04ME00223

Parcel: 136071950

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/14/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ ALL CORRECTIONS HAVE BEEN MADE.
05/13/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*/ PLEASE HAVE YOUR CONTRACTOR CALL FOR AN INSP WHEN SOMEONE WILL BE HOME.
05/06/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) THE PLUG ON THE CONDENSATE PUMP CANNOT BE CUT OFF AND WIRED DIRECT INTO THE FURNACE. PROVIDE A HOSE CLAMP WHERE PLASTIC HOSE CONNECTS TO PUMP. 2) #8 WIRE NOT ADEQUATE FOR A 60 AMP BREAKER. REDUCE THE SIZE OF BREAKER OR CHANGE WIRE TO #6. IDENTIFY CIRCUIT BREAKER.