Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04ME00207
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/04/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) BLOCK AND CLAMP THE GAS LINE ON ROOF 3/8" I.D. X 24" GAS FLEX IS NOT ADEQUATE FOR 120,000 BTU. 2) 50 AMP CIRCUIT IS TOO LARGE. SEE UNIT DATA PLATE FOR PROPER CIRCUIT. |