Permit: T04ME00205

Parcel: 135031100


Addresses:

6550 E CALLE CASTOR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/05/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ GAS PRESSURE TEST OK. ALL CORRECTIONS HAVE BEEN MADE.
04/23/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) YOU CANNOT USE WHITE WIRE FOR HIGH VOLTAGE. PUT BLACK TAPE ON WIRES. 2) MAX FUSE SIZE IS 35 AMPS. FUSES ARE 40 AMP. 3) 40 AMP BREAKER EXCEEDS MANUFACTURERS REQUIREMENT. 35 AMP IS MAX. 4) YOU MUST USE A BOND BUSHING AT CONNECTION TO CIRCUIT PANEL IF YOUR FITTING DOES NOT COMPLETELY COVER THE CONCENTRI KNOCK OUT. REDUCER WASHER ON OUTSIDE ALSO MUST COVER THE KNOCK OUT. DO NOT USE A CHASE NIPPLE TO CONNECT TO A PANEL. TAPE WHITE WIRE WITH BLACK TAPE. YOU CANNOT USE A CUTLER HAMMER BREAKER IN A MURRAY PANEL. 5) REMOVE THE UNION IN THE ATTIC ON THE GAS LINE AND USE REVERSE THREAD COUPLING AND NIPPLE IF NECESSARY. PROVIDE A 10 LB. MIN. TEST ON NEW GAS PIPE. YOU CAN INSTALL A SHUT OFF VALVE IN ATTIC AND TEST NEW SECTION OF PIPE.