Permit: T04ME00194

Parcel: 126132450


Addresses:

436 S DESERT AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/12/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ ALL CORRECTIONS HAVE BEEN MADE. OK TO ENERGIZE GAS LINE.
05/03/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*. DENIED. Do not use a chase nipple to connect to the circuit panel. Also provide a bond bushing if using reducer washers. Do not use the white neutial wire for the equipment ground. Use the ground wire supplied with the romex for its intended use. Connect gas pipe inside closet and then pressure test. You can use a shut off valve in the closet. Do not connect with a union. Recall for inspection.
04/15/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) ELECTRICAL FITTINGS NOT CONNECTED TO A/C UNIT. 2) PROVIDE A ROOF JACK WHERE CONDENSATE DRAIN PENETRATES THE ROOF. PAINT PVC WITH LATEX PAINT. 3) DISCONNECT THE WHITE NEUTRAL WIRE IN THE ELEC. DISCONNECT, CAP IT OFF, AND USE THE GROUND WIRE SUPPLIED WITH THE ROMEX FOR ITS INTENDED PURPOSE. NEED ACCESS TO ELEC CIRCUIT PANEL. 4) NEED TO SEE WHERE GAS PIPE IS CONNECTED. PROVIDE A MIN. 10 LB. PRESSURE TEST ON NEW PIPING.