Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ 1) CORRECTIONS HAVE BEEN MADE | |
| 08/04/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/24/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 60 AMP FUSES ARE TOO LARGE. 40 AMP IS MAX. #8 WIRE IS REQUIRED FROM DISCONNECT TO A/C UNIT. 2) CONDENSATE CAN NO LONGER TERMINATE DIRECTLY INTO A SEWER VENT. CALL JIM AT 909-4712, TO DISCUSS ALTERNATE METHODS. 3) USE AN APPROVED BASE TO SUPPORT CONDENSOR END OF A/C UNIT. CINDER BLOCKS WILL NOT BE ACCEPTED. |