Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04ME00164
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection : See detailed listing on site.| 999*.APPROVED. 13 PSI test okay. All corrections have been made. |
|
| 04/29/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CONDENSATE DRAIN NEEDS FLASHING AT ROOF PENETRATION. 2) GAS PRESSURE TEST., 7 LBS NOT MAINTAINING 10 PSI MIN. |
|
| 04/16/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) PROVIDE A MINIMUM 10 POUND PRESSURE TEST ON NEW GAS PIPE 2) YOU CANNOT USE A DIFFERENT MANUFACTURERS BREAKER IN THE CIRCUIT PANEL. BREAKER MUST BE SQUARE D. DO NOT USE A CHASE NIPPLE TO CONNECT TO CIRCUIT PANEL. USE AN APPROVED FITTING #8 WIRE NOT ADEQUATE FOR 60 AMP. USE #6 WIRE. IF USING ROMEX YOU HAVE TO DE-RATE THE ? DRAW AND USE #4 WIRE. YOU CANNOT USE A WHITE WIRE FOR LINE VOLTAGE. PLEASE VERIFY PERMIT FOR PANEL UPGRADE. CONDENSATE CANNOT DRIP ONTO A ROOF. MUST GO TO WITHIN 6" OF THE GROUND. DO NOT DRAIN ONTO A HARD SURFACE |