Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04ME00164

Parcel: 127070440


Addresses:

5112 E ALBERTA DR


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04ME00164

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2004 MECHANICAL - FINAL Approved IVRS - Inspection :
See detailed listing on site.| 999*.APPROVED. 13 PSI test okay. All corrections have been made.
04/29/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) CONDENSATE DRAIN NEEDS FLASHING AT ROOF PENETRATION. 2) GAS PRESSURE TEST., 7 LBS NOT MAINTAINING 10 PSI MIN.
04/16/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) PROVIDE A MINIMUM 10 POUND PRESSURE TEST ON NEW GAS PIPE 2) YOU CANNOT USE A DIFFERENT MANUFACTURERS BREAKER IN THE CIRCUIT PANEL. BREAKER MUST BE SQUARE D. DO NOT USE A CHASE NIPPLE TO CONNECT TO CIRCUIT PANEL. USE AN APPROVED FITTING #8 WIRE NOT ADEQUATE FOR 60 AMP. USE #6 WIRE. IF USING ROMEX YOU HAVE TO DE-RATE THE ? DRAW AND USE #4 WIRE. YOU CANNOT USE A WHITE WIRE FOR LINE VOLTAGE. PLEASE VERIFY PERMIT FOR PANEL UPGRADE. CONDENSATE CANNOT DRIP ONTO A ROOF. MUST GO TO WITHIN 6" OF THE GROUND. DO NOT DRAIN ONTO A HARD SURFACE