Permit: T04ME00155

Parcel: 136086730

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/11/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/03/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*. DENIED. Use only Cutter Hammer(?) breaker. You can use a split bolt conector for splicing inside panel from alum. to copper. Recall for inspection.
04/28/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :
See detailed listing on site.| 999$/ 1) FAN COIL CIRCUIT BREAKER TOO LARGE AT 60 AMP. 50 AMP IS MAX WITH 7KW HEAT STRIP. RECALL FOR INSP.